40012 Herz
Flow controller

calculation and selection
85 % - model rating
Drawing 40012 Herz Flow controller Scheme 40012 Herz Flow controller
Data sheet
Техническое описание

buy a 40012 Herz in United States

No supplier Herz from United States is registered in our catalog
Register and our visitors will become your customers

[0] priority

add company

Model
40012
Manufacturer
Country
Austria
Allowable working fluids
Water
Function
maintains a set water flow rate at the installation place
Action
closes when the flow rate increases
Working position
normally open
Installation of electric actuator
impossible
PN
16
Tmax (for water)
100 °C
Tmin (for water)
-20 °C
Connection type
external thread
Body material
brass
Kvs m³/h
dP= 0.0 kPa

technical
specifications
price

DN
mm
L
mm
Kvs
m³/h
dG
m³/h
dP
bar
price
15 66 - 0.040 - 0.40
0.020 - 2.00
add your price
20 76 - 0.080 - 0.90
0.020 - 2.00
add your price
25 76 - 0.10 - 1.50
0.030 - 2.00
add your price
32 114 - 0.20 - 2.50
0.020 - 2.00
add your price
40 132 - 0.40 - 4.00
0.030 - 2.00
add your price
50 140 - 0.50 - 5.00
0.040 - 2.00
add your price

DN - nominal diameter, mm.

L - length along the pipeline axis, mm.

dG - flow setting range, m³/h.

dP - pressure loss range on the controller, bar.

Kvs - flow capacity, corresponds to water flow rate in m³/h at which the pressure drop on the controller will be 1 bar.

question : comment : feedback

where to notify about the reply. not published anywhere
water flow rate
to maintain
m³/h

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in United States. Join the community and you will receive emails with requests for work in United States from our visitors.

design
installation
service
heating
water supply
conditioning