Warning: file_get_contents(http://ip-api.com/json/3.16.67.54?fields=country,currency): failed to open stream: HTTP request failed! in /home/teren/public_html/blocks/folder.php on line 19
TR 7122 RTK - Self-acting temperature controller

TR 7122 RTK
Self-acting temperature controller

production of discontinued

calculation and selection
102 % - model rating
Drawing TR 7122 RTK Self-acting temperature controller Design TR 7122 RTK Self-acting temperature controller
Техническое описание
Model
TR 7122
Manufacturer
Country
Germany
Allowable working fluids
Water | Steam | Compressed air
Function
maintains the set temperature
Action
closes when the temperature increases
Working position
-
PN
40 / 25 / 16
Tmax (for water)
175 °C
Tmin (for water)
0 °C
Connection type
flanged
Body material
cast iron / steel
Tmax for temperature sensor
t +50 °C

Length of impulse tube
2 | 4 | 6 | 8 m
Kvs m³/h
dP= 0.0 kPa

technical
specifications
price

DN
mm
Kvs
m³/h
dPmax
bar
L
mm
Xp
°C
Tc
seс
dT
°C
price
25 9.2
25 160 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





32 15
25 180 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





40 24
25 200 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





50 37
25 230 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





65 61
22 290 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





80 82
15 310 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





100 110
3 350 - - 0 - 70
30 - 100
50 - 120
80 - 150
100 - 170
130 - 200
production of discontinued





DN - nominal diameter, mm.

Тс - time constant, sec.

L - length along the pipeline axis, mm.

dT - range of temperatures maintained by the controller, °C.

dPmax - maximum pressure drop across the controller, bar.

Xp - proportional band corresponds to the temperature deviation in °C from the setpoint at which the valve of the controller will go to the extreme position.

Kvs - flow coefficient, corresponds to the water flow rate in m³/h at which the pressure drop across the controller will be 1 bar.

question : comment : feedback

where to notify about the reply. not published anywhere
Kvs
flow capacity
m³/hr
temperature
set
°C

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in Land of dreams. Join the community and you will receive emails with requests for work in Land of dreams from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website

about us

our library

Land of dreams

add your company to the catalog