Maintenance and repair of direct-acting temperature regulators

Maintenance of direct-acting temperature controllers should be performed in accordance with the operating instructions and the recommendations below should be taken into account.

  • Once a month, it is recommended to check the setting temperature using a control thermometer.
  • Every six months, it is recommended to measure the hysteresis, time constant, and proportionality zone, comparing them with the values obtained during commissioning.
  • If there are metering devices, it is recommended to measure the pressure drop in the fully open and leakage in the fully closed valve every six months, comparing them with the values obtained during commissioning.
  • The mesh filter installed before the temperature controller should be cleaned as it becomes clogged. The clogging of the filter is determined by the readings of the gauges installed before and after it.

Repair of the temperature controller may be required if it fails to maintain the temperature. Reasons for the temperature controller failure are:

  • Thermal element failure due to mechanical damage to the impulse line or temperature sensor. Most thermostatic drives cannot be repaired and require replacement.
  • Valve boiling. It can be eliminated by cleaning the disc and seat after dismantling the temperature controller.

Direct-acting temperature controllers are reliable devices and rarely fail. Therefore, if you notice a deviation in temperature from the set value, before looking for the cause in the controller, check if the operating mode matches the calculated one.

question : comment : feedback

where to notify about the reply. not published anywhere

211

Kvs
Flow coefficient
m³/h
Temperature set
°C
add your product to the catalog

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in United States. Join the community and you will receive emails with requests for work in United States from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website
about us
3 554 visitors yesterday
visitors per month
32 052 from United States
80 570 from all countries

Made in Ukraine

Subscribe

We do not sell equipment. Our goal is to help calculate and select the appropriate equipment. Companies can register on this website, add their equipment, and specify its price.