DR 7521 RTK - Pressure reduction controller

DR 7521 RTK
Pressure reduction controller

production of discontinued

calculation and selection
92 % - model rating
Drawing DR 7521 RTK Pressure reduction controller Design DR 7521 RTK Pressure reduction controller
Installation and operation instruction
Техническое описание
Model
DR 7521
Manufacturer
Country
Germany
Allowable working fluids
Water | Steam | Compressed air
Function
maintains a set pressure at the point of connection of the impulse line
Action
closes when the pressure increases
Working position
normally open
PN
40 / 25 / 16
Tmax (for water)
130 °C
Tmin (for water)
2 °C
Connection type
flanged
Body material
cast iron / steel
Kvs m³/h
dP= 0.0 kPa

technical
specifications
price

DN
mm
Kvs
m³/h
L
mm
dP
bar
price
15 3.30 130 0.050 - 0.40
0.10 - 0.90
0.18 - 1.50
0.34 - 2.00
0.60 - 3.00
0.80 - 4.70
1.50 - 8.60
3.00 - 14
production of discontinued






20 6.00 150 0.050 - 0.40
0.10 - 0.90
0.18 - 1.50
0.34 - 2.00
0.60 - 3.00
0.80 - 4.70
1.50 - 8.60
3.00 - 14
production of discontinued






25 9.20 160 0.050 - 0.40
0.10 - 0.90
0.18 - 1.50
0.34 - 2.00
0.60 - 3.00
0.80 - 4.70
1.50 - 8.60
3.00 - 14
production of discontinued






32 15 180 0.10 - 0.30
0.20 - 0.80
0.34 - 1.30
0.70 - 1.80
1.20 - 3.00
1.50 - 3.60
2.70 - 6.60
5.40 - 11
production of discontinued






40 24 200 0.10 - 0.30
0.20 - 0.80
0.34 - 1.30
0.70 - 1.80
1.20 - 3.00
1.50 - 3.60
2.70 - 6.60
5.40 - 11
production of discontinued






50 37 230 0.10 - 0.30
0.20 - 0.80
0.34 - 1.30
0.70 - 1.80
1.20 - 3.00
1.50 - 3.60
2.70 - 6.60
5.40 - 11
production of discontinued






65 42 290 0.10 - 0.30
0.20 - 0.80
0.34 - 1.30
0.70 - 1.80
1.20 - 3.00
1.50 - 3.60
2.70 - 6.60
5.40 - 11
production of discontinued






80 44 310 0.10 - 0.30
0.20 - 0.80
0.34 - 1.30
0.70 - 1.80
1.20 - 3.00
1.50 - 3.60
2.70 - 6.60
5.40 - 11
production of discontinued






DN - nominal diameter, mm.

dP - setting range, bar.

L - length along the pipeline axis, mm.

Kvs - flow capacity, corresponds to the water flow rate in m³/h at which the pressure drop across the regulator will be 1 bar.

question : comment : feedback

where to notify about the reply. not published anywhere
Kvs
flow capacity
m³/hr
pressure
set
bar

community of experts

We are gathering a community of experts in the design, installation, and service of heating, hot water, and water supply systems in Land of dreams. Join the community and you will receive emails with requests for work in Land of dreams from our visitors.

design
installation
service
heating
water supply
conditioning
dealers
advertising on the website

about us

our library

Land of dreams

add your company to the catalog